![]() |
This guide should
be read in conjunction with, but never as a substitute for BS5839
Part 1: 2002. The full fire safety system specification shall be
agreed between the responsible persons, which may include the local
fire authority, the fire safety consultant, health and safety
officer, system installer and the insurance company.
Risk Assessment Further to recent changes to the fire act, fire officers will no longer issue fire certificates for buildings. Ensuring that a building is safe for the occupants is now the responsibility of the employer. Insurance companies may refuses to insure buildings that have not had a risk assessment carried out. Fire officers are planning to carry out spot-checks on buildings without giving prior notice. As the new requirements are backed by criminal law, failure to have carried out risk assessments or operating in an unsafe environment may render the employer liable to court action, heavy fines and possibly imprisonment.
|
| Zone Requirements | |
|
|
Only one zone is required if the total floor area is not greater than 300m² |
|
|
The total area of a zone must not exceed 2000m² (Dependent on the risk present) |
|
|
The maximum search distance for a zone fire shall not exceed 60m |
|
|
Where stairwells or similar extend beyond one floor but are in one fire compartment, the stairwell shall be a separate zone |
|
|
If the zone covers more than one compartment, the zone boundaries shall follow compartment boundaries |
|
|
If the building is split into several occupancies, no zone shall be split between two occupancies |
|
Classification (Property or Life) Category P Systems Category P systems are automatic fire detection systems where the objective is to protect property. Categories are subdivided into the following systems: |
| P1 |
The objective of a category P1 system is to reduce the time from the discovery of a fire to the arrival of the fire brigade to a minimum. P1 systems should have fire detectors installed throughout all areas of the building. Unless combined with category M, in a category P system it may be adequate for alarm signals simply to allow fire fighting action to be taken, for example a signal to alert a responsible person to call the fire brigade. |
| P2 |
Category P2
systems are intended to provide an early warning of fire in areas of
high hazard, or to protect high-risk property. Automatic fire
detection should be installed in defined areas of a building.
|
|
Category LSystems Category L systems are automatic fire detection systems where the objective is to protect life. Categories are subdivided into the following systems: |
| L1 |
This is the highest category for the protection of life and is intended to give the earliest possible notification of a fire in order to allow maximum time for evaluation. Automatic and manual fire detection should be installed throughout all areas of the building with smoke detectors employed wherever possible to protect rooms in which people are expected to be present. All alarm signals given in a category L system must be sufficient to warn people for whom the alarm is intended to allow time for an evacuation. |
| L2 |
Intended to offer early notification of a fire allow evacuation
before escape routes becomes smoke filled. Automatic fire detection
should be specified in defined areas in addition to L3 and
additional protection should be provided in rooms at higher risk.
|
| L3 |
As with L2, category L3 is intended to offer early notification of a
fire to allow evacuation before escape routes become smoke filled.
Smoke or heat detectors should be installed in escape routes and in
rooms opening onto escape routes.
|
| L4 |
Category L4 is designed to offer protection to the escape routes
from a building and should comprise category M plus smoke detectors
in corridors and stairways.
|
| L5 |
Category L% is a non-prescriptive system in which the protected
areas are designed to satisfy a specific fire risk objective other
than that of L1 to L4. Within the building, certain areas defined
but the fire system specification are protected by automatic fire
detection in order to reduce risk to life. Category L5 may also
include manual fire protection.
|
|
Category M Systems Category M systems are reliant on human intervention and use only manually operated fire detection such as break glass call points. category M systems should only be employed if there are no persons sleeping in the building and if a fire is likely to be detected by people before escape routes are affected. Any alarm signals given in a category M system must be sufficient to ensure that any persons within the alarm areas are warned of a fire condition. |
| Break Glass Call Point Positioning | |
|
|
Break glass call
points shall be located on exit routes and in particular on the
floor landings of stairs cases and at all exits to the open air
|
|
|
Dependent upon
the risk, break glass call points shall be located so that no person
needs to travel more than 45m from any position
|
|
|
General call
points shall be fixed 1.4m above the floor in easily accessible,
well-illuminated and conspicuous positions clear of any obstruction
|
|
|
Detection devices
may be installed on the same system, though it is advisable to
install call points on separate zones where automatic detection
needs to be delayed
|
| Alarm Sounders | |
|
|
A minimum sound
level of 65dBA or 5dBA above any background noise likely to persist
for longer than 30 seconds is required at any point in an occupied
building
|
|
|
If the alarm
systems is to used in buildings such as hotels, a minimum sound
level 75dBA at the bed head is required in order to wake a sleeping
person.
|
|
|
Audible warning
devices should have a similar sound and distinct from alarms used
for other purposes, and noisy areas may require high output sounders
|
|
|
To prevent alarm
sounds from exceeding comfortable levels, the use of a greater
number of quieter sounders, should be considered
|
|
|
Two sounder
installed on two independent circuits must be used be used on a fire
system so that a failure on one circuit does not cause a total
failure of all sounders
|
|
|
Most standard
doors will cause a 20dB drop in sound levels. Fire doors will cause
a drop of 30dB
|
|
|
For P systems, a
red external sounder marked 'FIRE ALARM' is required
|
|
|
When mains
voltage sounders are used in addition to 24V DC sounders, the mains
sounder supply must be monitored
|
| Smoke Detectors | |
|
|
Optical smoke
detectors are designed to rapidly detect visible and invisible smoke
particles, in the range of 0.2µm to 60µm. An optical arrangement is
located within a light proof chamber, which triggers the detector
when smoke enters the chamber
|
|
|
Smoke detection
devices have an individual coverage of 7.5m radius. However, these
radii must overlap to ensure there are no 'blind spots'. Therefore,
the individual coverage can be represented by a square measuring
10.6m x 10.6m giving an actual area coverage of 112m² per device
|
| Heat/Rate of Rise Detectors | |
|
|
Fixed temperature
heat detectors are suitable in environments where there is a high
ambient temperature or in areas where sudden changes in the ambient
temperatures are common e.g. boiler rooms, drying rooms, kitchens
|
|
|
Rate of rise
detectors are designed to detect a fire as the temperature
increases. They incorporate a fixed upper temperature limit if the
rate of temperature increase has been too slow to trigger the
detector earlier. These detectors are suitable where the ambient
temperature is stable and a fast to sudden temperature increase is
required, for example, areas unsuitable for smoke detection due to
dust or other contamination
|
|
|
Heat detection
devices have an individual coverage of 5.3m radius. However these
radii must overlap to ensure there are no 'blind spots'. Therefore
individual coverage can be represented by a square measuring 7.5m x
7.5m giving an actual coverage of 56-25m² per device
|
| Detector Selection |
| Type of Detector | Ideal Application | Unsuitable |
| Ionisation Smoke Detector | General Purpose. Ideal for fast flaming fires | Unsuitable for areas, subjected to smoke, steam dust or dirt during normal use |
| Optical Smoke Detector | General Purpose. Ideal for smoldering fires | Unsuitable for areas, subjected to smoke, steam dust or dirt during normal use |
| Combined Optical Smoke/Heat Detector | General Purpose. Ideal for both fast flaming and smoldering fires | Unsuitable for areas, subjected to smoke, steam dust or dirt during normal use |
| Optical Beam Smoke Detector | Large and high rooms | Unsuitable for areas, subjected to smoke, steam, dust or dirt during normal user |
| Rate of Rise Heat Detector | Areas subjected to smoke, steam, dust or dirt during normal use | Unsuitable for areas, subjected to temperatures of over 43ºC and rapid changes of temperature |
| 58ºC Fixed Heat Detector | Areas subjected to smoke, steam, dust or dirt and rapid changes of temperature during normal use | Unsuitable for areas, subjected to temperatures of over 43ºC |
| 78ºC Fixed Heat Detector | Areas subjected to smoke, steam, dust or dirt and temperatures over 43ºC during normal use | Unsuitable for areas, subjected to temperatures of over 70 |
| Maximum Ceiling Heights for Detectors |
| Type of Detector | Maximum Ceiling Height |
| EN54-7 Smoke Detector |
10.5m
|
| EN54-5 Class A1 58ºC Heat Fixed Detector |
9m
|
| EN54-5 Class B 78ºC Heat Fixed Detector |
6m
|
| Optical Beam Smoke Detector |
25m
|
| VISUAL DESIGN GUIDE |
![]() |
![]() |
|
The sounder
device should give a minimum sound level of
65dB(A) or 5dB(A)
above any background noise lasting more than
30 seconds. It shall operate at 500Hz to
1000Hz
|
A person
searching a zone for a fire should not have to travel more than
60m to identify the
source of a fire. A person should not have to travel more than
45m to reach a manual
call point.
|
![]() |
![]() |
|
Manual Callpoints
should be positioned1.4m (/-200mm)
from floor level. Any non-mechanically protected cable medium should
have additional protection up to 2m
from floor level.
|
Cabling to the
sound device should be arranged so in the event of a fault occurring
during a fire condition, at least one sounder device will remain
operational. Any metallic parts of fire systems including cabling
and conduit should be well separated from any lighting protection
system.
|
![]() |
![]() |
|
Smoke detection
devices have an individual coverage 7.5m
radius. However, these radii must overlap to ensure there are no
'blind spots'. Therefore, the individual coverage can be represented
by a square measuring 10.6m x 10.6m
giving an actual area coverage of 112m²
per device
|
Heat detection
devices have an individual coverage of 5.3m
radius. However, these radii must overlap to ensure there are no
'blind spots'. Therefore, the individual coverage can be represented
by a square measuring 7.5m x 7.5m
giving an actual area coverage of 56.25m²
per device.
|
![]() |
![]() |
|
For ceilings that
feature an apex, if the height of the apex is less than
150mm from the rest of
the ceiling for heat detectors and 600mm from the rest of the
ceiling for smoke detectors, they can be treated the same as flat
ceilings. For higher apexes, a device should be installed at the
highest point. The distance to adjacent devices can be increased by
1% per1 degree of the angle of the roof. Up to a maximum of 25%
|
Limits of ceiling heights |
![]() |
![]() |
|
For areas where
people are sleeping, sounder devices should produce a minimum of
75dBA at the bed-head
with all doors shut.
|
Decibel loss
occurs through doors: -20dBA
through a normal door, -30bDA
through a fire door.
|
![]() |
![]() |
|
In corridors less
than 2m wide, the
horizontal spacing of detectors may be increased. The areas of
coverage need not overlap as in the case of a room. Any corridor
over 2m wide is deemed a
room and device spacing should follow the standard for rooms.
|
In corridors less
than 2m wide, the
horizontal spacing of detectors may be increased. The areas of
coverage need not overlap in the case of a room. Any
corridor over 2m wide is
deemed a room and device spacing should follow the standard for
rooms.
|
![]() |
![]() |
|
Do not site
detectors less than 1m
from air inlets or air conditioning units.
|
Detectors should
not be mounted within 500m
of any obstruction. If the opt of a solid
partition is less than 300mm
from the ceiling, it should be treated as a wall. Similarly, ceiling
obstructions such as beams should be treated as walls if they are
deeper than 10% of the
ceiling height.
|
![]() |
![]() |
|
Fire resistant
cabling is required within the whole fire alarm system including the
mains supply cables. The user of non-fire resisting cables will no
longer comply with BS5839.
|
Never mount
detectors closer than twice the depth of luminaire
|
![]() |
![]() |
|
Voids less than
800mm in height need not
have independent coverage, unless fire or smoke is able to spread
from one area to another through the void or this risk assessment
shows an AFP (Automatic Fire Protection) to be necessary.
|
Vertical shafts
like lifts and stairways should have a detector mounted within
1.5m of any opening.
Enclosed stairways should have a detector on each main landing.
|
![]() |
![]() |
|
The sensing
element of a heat detector (Themistor) should not be less than
25mm below the ceiling
and not greater than 150mm
below the ceiling.
|
The sensing
element of a smoke detector (Photoelectric chamber) should not be
less than 25mm below the
ceiling and not greater than 600mm
below the ceiling.
|
|
This guide should
be read in conjunction with, but never as a substitute for BS5839
Part 1: 2002.
|
luminaire
emergency lighting ballast exit sign orbik spel fire central battery gear
detection pcb can baton freznel ip65 ip52 ip50 ip20 ip25 maintained uk UK